ALPHABETIC REFERENCE
Parameter
Number
8
9
10
11
13
15
16
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
The rotational mode switches an XFM 36-1/R load independent of its rank in the
group (Parameter P14 [Load Number]). Each XFM 36-1/R in a group counts the
duration (in seconds) of its ON status and stores it in Parameter P8. It stores its
OFF status in Parameter 9.The maximum value of all P8s in a priority group is
stored in user address IA___On_Index_P1/2/3. The maximum value of all P9s is
stored in IA___Off_Index_P1/2/3. The next load that can switch on is the XFM 36-
1/R that has the greatest Switch Off Index (P9) value and the next one that can
switch off is the XFM 36-1/R that has the greatest Switch On Index (P8) value in
the group.
The criteria for rotational switching ON a load are as follows:
• The XFM 36-1/R is in automatic operating mode (Parameter P13 = 0).
• Parameter P15/16/17 in XFM 35 is 0 and user address ID___Rotating_P1/2/3 is
1. (ID___Rotating_P1/2/3 is not required for XFM 36-1R.)
• The power value at the first input Po is positive and equal or greater than the load
power Parameter P15 of the XFM 36-1/R.
• The value of the user address IA___Off_Index_P1/2/3 is less than or equal to the
XFM 36-1/R switch-off index Parameter P9 (for example, XFM 36-1/R is in the
third priority group; the value of IA___Off_Index_P3 is 105600; and the switch-off
index Parameter P9 has the same value 105600).
• The minimum OFF time (Parameter P11 of the XFM 36-1/R) has expired.
• If Parameter P16 of the XFM 36-1 is 1, input RM must also be 1 (see the RM
Functions description later in this section for details).
• User addresses ID___Peak_load and ID___Shutdown are 0 (that is, the peak
load and shutdown functions are not active).
The criteria for rotational switching OFF a load are as follows:
• The XFM 36-1/R is in automatic operating mode (Parameter P13 = 0).
• Parameter P15/16/17 in XFM 35 is 0 and user address ID___Rotating_P1/2/3 is
1.(ID___Rotating_P1/2/3 is not required for XFM 36-1R.)
• The power value at the first input Po is negative.
• The value of the user address IA___On_Index_P1/2/3 is less than or equal to the
XFM 36-1/R switch-on index Parameter P8 (for example, XFM 36-1/R is in the
second priority group; the value of IA___On_Index_P2 is 145265, and the switch-
on index Parameter P8 has the same value 145265).
• The minimum ON time (Parameter P10 of the XFM 36-1/R) has expired.
The following table lists the parameters used for the rotational switching of loads:
Type
Description
Display
Switch On Index (time load has been ON)
Display
Switch Off Index (time load has been OFF)
Comm.
Minimum ON Time
Comm.
Minimum OFF Time
Comm.
Mode of Operation
0=Auto; 1=ON; 2=OFF
Progr.
Power of the Load
Progr.
Feedback -Op_Mode
0=RM for status_feedback
1=RM AND Po
2=No RM function
116
EXCEL CARE CONTROL ICONS
Setting
Default
Range
Value
none
none
none
none
0-300
60
0-400
60
0/1/2
0
0-1000
1000
0/1/2
2