EXCEL CARE CONTROL ICONS
ALPHABETIC REFERENCE
Module 2 Humidify/Dehumidify
Based on the positioning signal from the basic humidity controller (X2), this module
decides whether there is a need to humidify or dehumidify. To ensure stability for
smaller deviations as well, the module establishes a hysteresis symmetrically
around the zero point of the basic controller (50 percent). It calculates the amount of
hysteresis in the same way as for Module 1 (15 percent of the working range).