Module 1 Heating/Cooling
Based on the positioning signal from the basic temperature controller (X1), this
module decides whether there is a need for heating or cooling. To ensure stability
for smaller deviations as well, the module establishes a hysteresis symmetrically
around the zero point of the basic controller (50 percent). It calculates the amount of
hysteresis as follows:
Hysteresis = P3 * 0.15
In other words, hysteresis is 15 percent of the working range.