Honeywell EXCEL 5000 User Manual page 106

Open system control icons
Hide thumbs Also See for EXCEL 5000:
Table of Contents

Advertisement

ALPHABETIC REFERENCE
User Address
ID___Rotating_P
IA___Off_Index_P
IA___On_Index_P
ID___Off_Prio
ID___On_Prio
ID___Peak_load
ID___Shutdown
XFM 36 Internal Parameters
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Input/
Type
Output
VD
Input
0:
1:
VA
Input/
1)
Output
2)
VA
Input/
1)
Output
2)
VD
Input/
0:
Output
1:
VD
Input/
0:
Output
1:
VD
Input
1:
0:
VD
Input
1:
0:
Type abbreviations:
VA: Virtual (pseudo) analog
VD: Virtual (pseudo) digital
The XFM 36-1, 36-1S, and 36-1R internal parameters dialog box lists parameters
that control program functions. Later sections describe how to use these parameters
depending on operation desired. The table following the dialog box summarizes
parameter types, functions, default values and engineering units. (The dialog box
values and entering units are not necessarily the defaults.)
108
EXCEL CARE CONTROL ICONS
Comment
Load switching is on sequential operating mode in the
group (XFM 36-1 only).
Load switching is on rotating operating mode in the group
(not with XFM 36-1S).
The greatest switch-off time of all previous loads (and this
load, if Output) in the group, if load switching is rotational.
No function, if load switching is sequential.
The greatest switch-on time of all previous loads (and this
load, if Output) in the group, if load switching is rotational.
The highest load number switched on in the group, if load
switching is sequential.
All previous loads (and this load, if Output) in the group are
OFF
There is at least one load in the group that is ON
All previous loads (and current, if output) in the group are
ON
There is at least one load in the group that is OFF
Signal to stop switching on the load
Signal is not active
Signal to shed the load immediately
Signal is not active