ALPHABETIC REFERENCE
Dead time short P8
Time constant short P9
Dead time long P10
Time constant long P11
Building model adaption P12
Room control P-band P13
Integral action time P14
Maximum flow
temperature P15
Heating curve curvature P16
Heating curve slope P17
Max. heating curve slope
for adaptation (with room sensor) P18
Heating curve
adaptation mode P19
Occupied/ unoccupied
changeover P20
Frost protection
Room temperature
multiplier P23
Minimum room
temperature P24
Differential minimum room
temperature P25
Parameter Number
Descriptions
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Number type: Whole number, Unit: Minutes
Default: 5 min, Range: 0 through 60 min
Number type: Whole number, Unit: Minutes,
Default: 75 min, Range: 0 through 2880 min
Number type: Whole number, Unit: Minutes
Default: 5 min, Range: 0 through 60 min
Number type: Whole number, Unit: Minutes
Default: 150 min, Range: 0 through 2880 min
Number type: Whole number, Unit: None
Default: 1, Range: 0 through 2, (0 = disabled; 1 = enabled, 2 = restart)
Number type: Decimal, Unit: %/K
Default: 10.0 K; Range: >=0
Number type: Decimal, Unit: Seconds
Default: 300.0 s, Range: >= 0
Number type: Decimal, Unit: Degrees Celsius
Default: 80.0 °C, Range: 0 through 150.0 °C
Number type: Decimal, Unit: none
Default: 1.33, Range: 0 through 2.0
Number type: Decimal, Unit: none
Default: 1.6, Range: 0 through 4.5
Number type: Decimal, Unit: none
Default: 4.5, Range: 0.4 through 4,5
Number type: Decimal, Unit: none
Default: 2, Range: 0 through 4; (0 = disabled; 1 = enabled, 2 = restart; 3 =
adaptation refreshed new start; 4 = direct RMT compensation
Number type: Decimal, Unit: Degree Celsius
Default: 16 °C, Range: 0 through 30 °C
limit P21
Number type: Decimal, Unit: Degree Celsius
Default: 2 °C, Range: 0 through 15 °C
Boost factor
P22
Number type: Decimal, Unit: none
Default: 1, Range: 0 through 30
Number type: Decimal, Unit: Degree Celsius
Default: 4 °C, Range: 0 through 50
Number type: Decimal, Unit: Degree Celsius
Default: 13 °C, Range: 0 through 30 °C
Number type: Decimal, Unit: Kelvin
Default: 2 K, Range: 0 through 10 K
P1 Minimum preheat time
P2 Maximum preheat time
P3 No room sensor compensation
168
EXCEL CARE CONTROL ICONS