Honeywell EXCEL 5000 User Manual page 233

Open system control icons
Hide thumbs Also See for EXCEL 5000:
Table of Contents

Advertisement

EXCEL CARE CONTROL ICONS
Attributes Table
CARE defaults residual priority to zero (X3=0) so that all commands from WIA are
accepted. You can set WIA to leave a higher residual.
The following table lists attributes that you can select for the various point types.
Note that the default values for most of these attributes can be changed via the
CARE Editors. See Excel CARE User Guide 74-5587 (US) / EN2B-0182 (Europe) ,
Editors chapter, for descriptions of these attributes. The attributes that are not
available to the CARE Editors are manual value, operating status, trend log, alarm
status, auto value, and hours run. These attributes are accessible via operator
terminals such as the Excel Building Supervisor (XBS) and the XI581/XI582. Excel
Building Supervisor Operator Manual 74-2039 describes the manual value,
operating status, alarm status, auto value, and hours run attributes for the related
point types. See Excel XI581/XI582 Operator Terminals Operator Manual 74-3554
(US) / EN2B-0126 (Europe) for trend logging information.
NOTE: The list of attributes presented in the icon change depending on the type of
connection. For example, if the output is connected to a digital type
connection (if it is a point or another icon), then the list of available
attributes consists of only the ones marked dig in this table. The same type
of list is available when an analog type connection is made; only the analog
are available.
A special condition exists when the attribute "Manual Value" is selected.
The available list only consists of Manual Value and No Attribute.
235
ALPHABETIC REFERENCE
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)