EXCEL CARE CONTROL ICONS
Descriptions
CYC Operation
Output Variations
P3 On time (seconds)
P4 Off time (seconds)
On time establishes the duration of the high level while Off time establishes the
duration of the low level. Software sends the sequence to Output Y as long as a
signal greater than or equal to 1 is present in Input X. Illustration:
The output cycles only while the input is 1:
If the OFF time is set to 0, a single positive pulse is generated:
If the ON time is set to 0, a single negative pulse is generated:
If the input is removed mid-cycle, the output continues to complete that cycle.
39
ALPHABETIC REFERENCE