Omron ERT1 Series Operation Manual page 75

Ethernet/ip slave units
Table of Contents

Advertisement

Screw-less Clamp Terminals
Indicators
Communications
Indicators
I/O Indicators
Setting the Node
Address
(2) Ethernet Connector
The network communications cable is connected to this connector.
(3) Power Supply Connector
The communications and Unit power supply is connected to this connector.
24 V DC
0 V DC
Applicable Ferrules
Manufacturer
Phoenix Contact
Nihon Weidmuller
(4) Communications Indicators: MS and NS
These indicators show the Unit communications status and network commu-
nications status.
(5) and (6) Terminal Blocks 1 and 2
The I/O devices and output power supply are connected to these terminal
blocks.
(7) and (8) I/O Indicators
These indicators show the ON/OFF status of the I/O and the error status of
connected devices.
Refer to 3-1-3 Communications Indicators.
The meanings of the input indicators are given in the following table.
Indicator name
Status
0 to 15
I/O
The rotary switches are used to set the lower digits of the IP address.
Setting method
Two hexadecimal digits
Setting range
01 to FE
Terminal
+
24 V DC
0 V DC
Model
AI-0.5-10
H 0.5/16 D
Color
Yellow
Lit yellow when input or output is
ON.
Red
Flashing red when the load is dis-
connected.
Automatically reset when the load
is connected.
Red
Lit red when the load is short-cir-
cuited.
Automatically reset when the
short-circuit is removed.
OFF
Not lit when input or output is OFF.
Green
Lit green when I/O power is being
supplied.
OFF
Not lit when I/O power is not being
supplied.
Section 4-2
Specification
Applicable wire size
2
0.5 mm
(AWG 20)
2
0.5 mm
(AWG 20)
Meaning (main error)