TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R/W
(2) AV
R/W
(2) AV
R
(5) BV
R/W
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(5) BV
R/W
(2) AV
R
(5) BV
R/W
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(5) BV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(5) BV
R/W
(2) AV
Johnson Controls Unitary Products
BACnet
Object
Inst
Descriptor
71
SPCE_ALM_TMP
72
SPCE_ALM_TIM
26
SEN_FAULT_EN
73
SP_OFF_RANGE
4
SUP_AIR_TEMP
70
SAT_ALM_COOL
53
SAT_ALM_HEAT
22
SAT_COOLING
3
SAT_COOL_SP
24
SAT_HEATING
52
SAT_HEAT_SP
34
SFAN_VFD_OUT
36
ALARM_1
37
ALARM_2
38
ALARM_3
39
ALARM_4
40
ALARM_5
29
TH_OFFSET
26
TEM_HUM_STPT
67
FAN_HEAT
2
UNOC_COOL_SP
51
UNOC_HEAT_SP
75
UNOC_OVR_TP
65
VAV_CL_LO_SP
66
VAV_SAT_RSET
64
VAV_CL_HI_SP
5
VAV_OCC_HEAT
60
VAV_OHEAT_SP
Default
Min
Max
Point Description
0
0
25
Space Sensor Alarm Temperature (degrees
F, 0 = disabled)
0
0
120
Space Sensor Alarm Time (minutes F, 0 =
disabled)
Space Sensor Fault Override (Construction
Mode) Enabled
3
0
5
Space Temprature Sensor Offset Range
(0-5 degrees)
Supply Air Temperature
0
0
80
Supply Air Temperature Alarm Setpoint for
Cooling
0
0
120
Supply Air Temperature Alarm Setpoint for
Heating
Supply Air Temperature Limit for Cooling
Enabled
50
40
65
Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
Supply Air Temperature Limit for Heating
Enabled
135
100
180
Supply Air Temperature Limit for Heating
Setpoint (degrees F)
Supply Fan VFD Output Status (0-100%)
System Alarm #1
System Alarm #2
System Alarm #3
System Alarm #4
System Alarm #5
5
1
10
Temperature/Humidity % Humidity that =
1°F of Offset
50
20
80
Temperature/Humidity Setpoint (percent
Humidity)
Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
85
45
99
Un-Occupied Cooling Setpoint
60
45
99
Un-Occupied Heating Setpoint
60
0
240
Unoccupied Override Time Period
55
40
70
VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
72
40
85
VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature)(degrees F)
60
40
70
VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
VAV Occupied Heating Enabled
68
40
85
VAV Occupied Heating Setpoint (degrees F)
514067-UAD-A-0509
9