514067-UAD-A-0509
TABLE 2: POINTS LIST IN DESCRIPTION ORDER
BACnet
Read/
Object
Write
Type
R
(2) AV
R
(2) AV
R
(5) BV
R/W
(2) AV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(2) AV
R
(5) BV
R/W
(2) AV
R/W
(2) AV
R
(5) BV
R
(5) BV
R
(5) BV
R/W
(2) AV
R
(5) BV
R
(5) BV
R
(2) AV
R
(2) AV
R
(5) BV
R/W
(2) AV
R
(2) AV
R
(5) BV
R
(5) BV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
4
BACnet
Object
Inst
Descriptor
14
ACC_OVER_TME
15
ACTIVE_ALARM
16
AIR_PROOF_SW
79
OAQ_STPT
85
ALARM_1_ON
86
ALARM_2_ON
87
ALARM_3_ON
88
ALARM_4_ON
89
ALARM_5_ON
33
BLDG_STATIC
29
BP_SENS_INST
57
BLDG_SP_STPT
25
COM_V_LOW_SP
34
CVM_COOLING
35
CVM_HEATING
33
COM_VENT_STA
24
COM_V_HI_SP
23
COOLING_ENA
21
FAN_ON_W_SEN
56
CV_VAV_SELEC
8
IAQ_VALUE
39
DEMAND_VENT
18
DEMVENT_STPT
67
REVISION
90
DF_SW_INST
15
DIRT_FILT_SW
35
DUCT_STATIC
58
DUCT_SP_STPT
59
DUCT_SD_STPT
31
ECO_DAMP_OUT
Default
Min
Max
Point Description
Accumulated Unoccupied Override Time
(in hours)
Active Alarm
Air Proving Switch Status (1=closed,
0=open/no air flow)
1000
0
5000
Air Quality Setpoint Outside
Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
Building Static Pressure
Building Static Pressure Sensor Installed
0.1
-0.25
0.25
Building Static Pressure Setpoint
70
60
85
Comfort Ventilation LowerSetpoint
(degrees F)
Comfort Ventilation Mode for Cooling
Enabled
Comfort Ventilation Mode for Heating
Enabled
Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
80
60
85
Comfort Ventilation Upper Setpoint
(degrees F)
Cooling Mode Enabled
CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
CV/VAV Selected (0= Valid CV, 1=Valid
VAV, 2= Invalid Value)
Demand Ventilation (IAQ) Value (PPM)
Demand Ventilation (using Inside Sensor)
Enabled
1000
0
5000
Demand Ventilation Setpoint
xx
Device Revision
Dirty Filter Switch Installed
Dirty Filter Switch Status (0=open,1=closed/
fault)
Duct Static Pressure
1.5
0
5
Duct Static Pressure Setpoint
4.5
0
5
Duct Static Pressure Shutdown Setpoint
Economizer Damper Output Status
(0-100%)
Johnson Controls Unitary Products