514067-UAD-A-0509
TABLE 3: POINTS LIST IN OBJECT ORDER
BACnet
Read/
Object
Write
Type
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
10
BACnet
Object
Inst
Descriptor
1
OCC_COOL_SP
2
UNOC_COOL_SP
3
SAT_COOL_SP
4
SUP_AIR_TEMP
5
RET_AIR_TEMP
6
SPACE_TEMP
7
AMB_TEMP
8
IAQ_VALUE
9
OAQ_VALUE
10
AMB_AIR_HUM
11
AMB_AIR_ENTH
12
RET_AIR_HUM
13
RET_AIR_ENTH
14
ACC_OVER_TME
15
ACTIVE_ALARM
16
NUMBER_COMPS
17
OP_COOL_STPT
18
DEMVENT_STPT
19
ECON_MIN_POS
20
ECO_1ST_STPT
21
ECO_2ND_STPT
22
ECON_OAEN_SP
23
ECON_OAT_ENA
24
COM_V_HI_SP
25
COM_V_LOW_SP
26
TEM_HUM_STPT
27
HGR_HUM_STPT
28
MAX_TH_OFSET
29
TH_OFFSET
30
MAX_DMV_ECON
31
ECO_DAMP_OUT
32
EXH_DAMP_OUT
33
BLDG_STATIC
34
SFAN_VFD_OUT
35
DUCT_STATIC
36
ALARM_1
37
ALARM_2
Default
Min
Max
Point Description
72
45
99
Occupied Cooling Setpoint
85
45
99
Un-Occupied Cooling Setpoint
50
40
65
Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
Supply Air Temperature
Return Air Temperature
Space (Indoor) Air Temperature
Outside Air Temperature
Demand Ventilation (IAQ) Value (PPM)
1000
0
5000
Outside Demand Ventilation (OAQ) Value
(PPM)
Outside Air Humidity
Outside Air Enthalpy
Return Air Humidity
Return Air Enthalpy
Accumulated Unoccupied Override Time (in
hours)
Active Alarm
Number of Compressors Available
Operating Cooling Setpoint
1000
0
5000
Demand Ventilation Setpoint
20
0
100
Economizer Minimum Position
55
40
65
Economizer First Stage Setpoint
50
40
65
Economizer Second Stage Setpoint
27
10
50
Economizer Outside Air Enthalpy Setpoint
55
40
80
Economizer Outside Air Temperature Enable
Setpoint
80
60
85
Comfort Ventilation Upper Setpoint (degrees F)
70
60
85
Comfort Ventilation LowerSetpoint (degrees F)
50
20
80
Temperature/Humidity Setpoint (percent
Humidity)
50
0
100
Hot Gas Reheat Humidity Setpoint (percent
Humidity)
3
0
5
Max Temperature/Humidity Setpoint Offset
5
1
10
Temperature/Humidity % Humidity that = 1°F
of Offset
50
0
100
Maximum Demand Ventillation Economizer
Position
Economizer Damper Output Status (0-100%)
Exhaust Damper Output Status (0-100%)
Building Static Pressure
Supply Fan VFD Output Status (0-100%)
Duct Static Pressure
System Alarm #1
System Alarm #2