Download Print this page

York LINC GATEWAY 514067-UAD-A-0509 Application Manual page 11

Simplicity network router user manual

Advertisement

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
Johnson Controls Unitary Products
BACnet
Object
Inst
Descriptor
38
ALARM_3
39
ALARM_4
40
ALARM_5
41
E_C1_ACM_HRS
42
E_C2_ACM_HRS
43
E_C3_ACM_HRS
44
E_C4_ACM_HRS
45
I_C1_ACM_HRS
46
I_C2_ACM_HRS
47
HGR_VLV_OUT
48
NUMBER_HEAT
49
OP_HEAT_STPT
50
OCC_HEAT_SP
51
UNOC_HEAT_SP
52
SAT_HEAT_SP
53
SAT_ALM_HEAT
54
OAT_HEAT_L_O
55
HW_VLV_OUT
56
CV_VAV_SELEC
57
BLDG_SP_STPT
58
DUCT_SP_STPT
59
DUCT_SD_STPT
60
VAV_OHEAT_SP
61
MWU_RAT_STPT
62
HYD_S1_SA_SP
63
HYD_S2_SA_SP
64
VAV_CL_HI_SP
65
VAV_CL_LO_SP
66
VAV_SAT_RSET
67
REVISION
Default
Min
Max
Point Description
System Alarm #3
System Alarm #4
System Alarm #5
Elite Compressor #1 Accumulated Run Time
(in hours)
Elite Compressor #2 Accumulated Run Time
(in hours)
Elite Compressor #3 Accumulated Run Time
(in hours)
Elite Compressor #4 Accumulated Run Time
(in hours)
Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)
Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)
Hot Gas Reheat Valve Output Status
(0-100%)
Number of Heat Stages Available
68
45
99
Operating Heating Setpoint
68
45
99
Occupied Heating Setpoint
60
45
99
Un-Occupied Heating Setpoint
135
100
180
Supply Air Temperature Limit for Heating
Setpoint (degrees F)
0
0
120
Supply Air Temperature Alarm Setpoint for
Heating
75
0
100
Outdoor Air Temperature HeatingLockout
Temperature
Hot Water Valve Output Status (0-100%)
CV/VAV Selected (0= Valid CV, 1=Valid VAV,
2= Invalid Value)
0.1
-0.25
0.25
Building Static Pressure Setpoint
1.5
0
5
Duct Static Pressure Setpoint
4.5
0
5
Duct Static Pressure Shutdown Setpoint
68
40
85
VAV Occupied Heating Setpoint (degrees F)
70
50
85
Morning Warm-Up and VAV Heating: Return
Air Temperature Setpoint (degrees F)
120
80
180
Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
150
80
180
Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
60
40
70
VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
55
40
70
VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
72
40
85
VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature) (degrees F)
0
0
xx
Device Revision
514067-UAD-A-0509
11

Advertisement

loading

This manual is also suitable for: