York LINC GATEWAY 514067-UAD-A-0509 Application Manual page 14

Simplicity network router user manual

Advertisement

514067-UAD-A-0509
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
BACnet
Read/
Object
Write
Type
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
14
Object
Inst
Descriptor
47
E_LPS2
48
E_HPS2
49
E_C2_OVRLOAD
50
E_CFAN1_STAT
51
E_COMP3_STAT
52
E_LPS3
53
E_HPS3
54
E_C3_OVRLOAD
55
E_COMP4_STAT
56
E_LPS4
57
E_HPS4
58
E_C4_OVRLOAD
59
E_CFAN2_STAT
60
E_GAS_VLVE1
61
E_LIMIT_ 1
62
E_GAS_VLVE2
63
E_LIMIT_ 2
64
E_GAS_VLVE3
65
E_LIMIT_ 3
66
E_FREEZE_ST
67
FAN_HEAT
68
HEAT_1_STAT
69
HEAT_2_STAT
70
HEAT_3_STAT
Default
Min
Max
Point Description
Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
Elite Compressor #3 Output Status (0=output
is OFF, 1=output is ON)
Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
Elite Compressor #4 Output Status (0=output
is OFF, 1=output is ON)
Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
Elite Gas Valve #1 Input Status
(1=energized, 0=not energized)
Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
Elite Gas Valve #2 Input Status
(1=energized, 0=not energized)
Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
Elite Gas Valve #3 Input Status
(1=energized, 0=not energized)
Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
Hot H2O Freeze Thermostat Switch #1 Input
Status (1=closed, 0=open/fault)
Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
Johnson Controls Unitary Products