York LINC GATEWAY 514067-UAD-A-0509 Application Manual page 15

Simplicity network router user manual

Advertisement

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R/W
(5) BV
Johnson Controls Unitary Products
BACnet
Object
Inst
Descriptor
71
I_IFAN_STAT
72
I_FAN_OVER
73
I_COMP1_STAT
74
I_LPS1
75
I_HPS1
76
I_COMP2_STAT
77
I_LPS2
78
I_HPS2
79
I_CFAN_STAT
80
I_GAS_VLVE1
81
I_LIMIT_1
82
I_FREEZE_1
83
I_FREEZE_2
85
ALARM_1_ON
86
ALARM_2_ON
87
ALARM_3_ON
88
ALARM_4_ON
89
ALARM_5_ON
90
DF_SW_INST
93
OCC_COMS_ENA
96
MANUAL_WRITE
Default
Min
Max
Point Description
Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
Intelli-Comfort Gas Valve #1 Input Status
Intelli-Comfort Limit Switch #1 Input Status
Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
Dirty Filter Switch Installed
Occupied Thermostat or Communication
Input Enabled
Manual Write Command to ModlINC
514067-UAD-A-0509
15

Advertisement

loading

This manual is also suitable for:

Simplicity linc