514067-UAD-A-0509
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R/W
(5) BV
R/W
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
12
BACnet
Object
Inst
Descriptor
69
OP_STPT_DIF
70
SAT_ALM_COOL
71
SPCE_ALM_TMP
72
SPCE_ALM_TIM
73
SP_OFF_RANGE
74
OAT_COOL_L_O
75
UNOC_OVR_TP
76
H1_ACCUM_HRS
77
H2_ACCUM_HRS
78
H3_ACCUM_HRS
79
OAQ_STPT
80
IO_DVNT_STPT
81
POP_HOURS
82
POP_MINUTES
84
ECON_RAEN_SP
1
OCCUPIED_ENA
2
HYDRONC_HEAT
3
HH_REVER_VLV
4
REM_CONT_ENA
5
VAV_OCC_HEAT
6
MORN_WARM-UP
7
ECONO_INST
8
PWR_EX_INST
9
MOD_EX_INST
10
EX_VFD_INST
11
MODBUS_ALARM
12
REDLINE
13
LOADSHED
14
LOW_SUP_VOLT
15
DIRT_FILT_SW
16
AIR_PROOF_SW
17
PURGE_SWITCH
18
HGR_STAT
Default
Min
Max
Point Description
1
1
5
Operating Setpoint Differential
0
0
80
Supply Air Temperature Alarm Setpoint for
Cooling
0
0
25
Space Sensor Alarm Temperature
(degrees F, 0 = disabled)
0
0
120
Space Sensor Alarm Time (minutes F,
0 = disabled)
3
0
5
Space Temprature Sensor Offset Range
(0-5 degrees)
45
0
100
Outdoor Air Temperature Cooling Lockout
Temperature
60
0
240
Unoccupied Override Time Period
–
–
–
Heating #1 Accumulated Run Time (in hours)
–
–
–
Heating #2 Accumulated Run Time (in hours)
–
–
–
Heating #3 Accumulated Run Time (in hours)
1000
0
5000
Air Quality Setpoint Outside
700
0
2000
Indoor/Outdoor Demand Ventilation Setpoint
4
0
23
Pre-Occupancy Purge Time (hours)
0
0
59
Pre-Occupancy Purge Time (minutes)
27
10
50
Economizer Return Air Enthalpy Setpoint
–
–
–
Occupied Enabled
–
–
–
Hydronic Heat Enabled
–
–
–
Hydronic Heat Reverse Actuated Valve
Installed
–
–
–
Remote Control Enabled
–
–
–
VAV Occupied Heating Enabled
–
–
–
Morning Warm-Up Enabled
–
–
–
Economizer Installed
–
–
–
Power Exhaust Installed
–
–
–
Modulating Exhaust Installed
–
–
–
Exhaust VFD Installed
–
–
–
Modbus Communication Alarm
–
–
–
Redline (0=clear redline, 1=set redline
operation)
–
–
–
Loadshed (0=clear loadshed, 1=set loadshed
operation)
–
–
–
Low Supply Voltage (0=comps not
overridden by LSV, 1=comps overridden)
–
–
–
Dirty Filter Switch Status (0=open,1=closed/
fault)
–
–
–
Air Proving Switch Status (1=closed,
0=open/no air flow)
–
–
–
Purge Switch Status (0=open,1=closed)
–
–
–
Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
Johnson Controls Unitary Products