York LINC GATEWAY 514067-UAD-A-0509 Application Manual page 12

Simplicity network router user manual

Advertisement

514067-UAD-A-0509
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
R
(2) AV
R
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R/W
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R/W
(5) BV
R/W
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
12
BACnet
Object
Inst
Descriptor
69
OP_STPT_DIF
70
SAT_ALM_COOL
71
SPCE_ALM_TMP
72
SPCE_ALM_TIM
73
SP_OFF_RANGE
74
OAT_COOL_L_O
75
UNOC_OVR_TP
76
H1_ACCUM_HRS
77
H2_ACCUM_HRS
78
H3_ACCUM_HRS
79
OAQ_STPT
80
IO_DVNT_STPT
81
POP_HOURS
82
POP_MINUTES
84
ECON_RAEN_SP
1
OCCUPIED_ENA
2
HYDRONC_HEAT
3
HH_REVER_VLV
4
REM_CONT_ENA
5
VAV_OCC_HEAT
6
MORN_WARM-UP
7
ECONO_INST
8
PWR_EX_INST
9
MOD_EX_INST
10
EX_VFD_INST
11
MODBUS_ALARM
12
REDLINE
13
LOADSHED
14
LOW_SUP_VOLT
15
DIRT_FILT_SW
16
AIR_PROOF_SW
17
PURGE_SWITCH
18
HGR_STAT
Default
Min
Max
Point Description
1
1
5
Operating Setpoint Differential
0
0
80
Supply Air Temperature Alarm Setpoint for
Cooling
0
0
25
Space Sensor Alarm Temperature
(degrees F, 0 = disabled)
0
0
120
Space Sensor Alarm Time (minutes F,
0 = disabled)
3
0
5
Space Temprature Sensor Offset Range
(0-5 degrees)
45
0
100
Outdoor Air Temperature Cooling Lockout
Temperature
60
0
240
Unoccupied Override Time Period
Heating #1 Accumulated Run Time (in hours)
Heating #2 Accumulated Run Time (in hours)
Heating #3 Accumulated Run Time (in hours)
1000
0
5000
Air Quality Setpoint Outside
700
0
2000
Indoor/Outdoor Demand Ventilation Setpoint
4
0
23
Pre-Occupancy Purge Time (hours)
0
0
59
Pre-Occupancy Purge Time (minutes)
27
10
50
Economizer Return Air Enthalpy Setpoint
Occupied Enabled
Hydronic Heat Enabled
Hydronic Heat Reverse Actuated Valve
Installed
Remote Control Enabled
VAV Occupied Heating Enabled
Morning Warm-Up Enabled
Economizer Installed
Power Exhaust Installed
Modulating Exhaust Installed
Exhaust VFD Installed
Modbus Communication Alarm
Redline (0=clear redline, 1=set redline
operation)
Loadshed (0=clear loadshed, 1=set loadshed
operation)
Low Supply Voltage (0=comps not
overridden by LSV, 1=comps overridden)
Dirty Filter Switch Status (0=open,1=closed/
fault)
Air Proving Switch Status (1=closed,
0=open/no air flow)
Purge Switch Status (0=open,1=closed)
Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
Johnson Controls Unitary Products