TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
Johnson Controls Unitary Products
BACnet
Object
Inst
Descriptor
19
LOW_AMB_OVRD
20
POP_ENABLED
21
FAN_ON_W_SEN
22
SAT_COOLING
23
COOLING_ENA
24
SAT_HEATING
25
HEATING_ENA
26
SEN_FAULT_EN
28
INTELLI-STRT
29
BP_SENS_INST
30
EX_FAN_STAT
31
ECONO_STATUS
32
FRECOOL_STAT
33
COM_VENT_STA
34
CVM_COOLING
35
CVM_HEATING
36
ECO_L_TO_SAT
37
OAH_SENSOR
38
RAH_SENSOR
39
DEMAND_VENT
40
E_IFAN_STAT
41
E_FAN_ OVER
42
E_COMP1_STAT
43
E_LPS1
44
E_HPS1
45
E_C1_OVRLOAD
46
E_COMP2_STAT
Default
Min
Max
Point Description
–
–
–
Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)
–
–
–
Pre-Occupancy Purge Enabled
–
–
–
CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
–
–
–
Supply Air Temperature Limit for Cooling
Enabled
–
–
–
Cooling Mode Enabled
–
–
–
Supply Air Temperature Limit for Heating
Enabled
–
–
–
Heating Mode Enabled
–
–
–
Space Sensor Fault Override (Construction
Mode) Enabled
–
–
–
Intelli-Start Enabled
–
–
–
Building Static Pressure Sensor Installed
–
–
–
Exhaust Fan Output Status (0=output is OFF,
1=output is ON)
–
–
–
Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
–
–
–
Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
–
–
–
Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
–
–
–
Comfort Ventilation Mode for Cooling
Enabled
–
–
–
Comfort Ventilation Mode for Heating
Enabled
–
–
–
Economizer Loading to Control Supply Air
Temperature Enabled
–
–
–
Outside Air Humidity Sensor Enabled
–
–
–
Return/Inside Air Humidity Sensor Enabled
–
–
–
Demand Ventilation (using Inside Sensor)
Enabled
–
–
–
Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
–
–
–
Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
–
–
–
Elite Compressor #1 Output Status (0=output
is OFF, 1=output is ON)
–
–
–
Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
–
–
–
Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
–
–
–
Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
–
–
–
Elite Compressor #2 Output Status (0=output
is OFF, 1=output is ON)
514067-UAD-A-0509
13