TROUBLESHOOTING

®
The Simplicity
LINC Gateway consists of two printed circuit
boards.
®
TABLE 4: SIMPLICITY
RS485 BOARD (Bottom)
Normal Board Operation
The PWR LED should be on during operation. The RX and TX
LEDs should flash when a signal is either received or sent.
Faulty Board Operation
If the PWR LED does not come on but the RX and TX flash, then
the PWR LED is broken.
If the TX and / or RX LEDs do not flash, it may represent a problem
with the field wiring or configuration problems in the field side of
the BacNET board. It may also indicate incorrect polling
parameters such as baud rate or parity.
Power Source
Frequency
Power Consumption
Operating Environment
Size (H x W x D)
Weight
Type
SDRAM Memory
FLASH Memory
Port 1 Type
Port 1 Speeds
Port 1 Connector
Port 2 Type
Port 2 Speeds
Port 2 Connector
LAN Cable
LEDs
Switch Selections
16
LINC GATEWAY
Normal Board Operation
LEDs LA and LB flash about once per second. LED GP105 will
remain on within 45-60 seconds after power up, signifying normal
operation. The PWR LED should be on during operation. The RX
and TX LEDs should flash when a signal is either received or
sent.
Faulty Board Operation
If the PWR LED does not come on but the RX and TX flash, then
the PWR LED is broken.
If the TX and / or RX LEDs do not flash, it may represent a
problem with the field wiring or confguration problems in the field
side of the BacNet board. It may also indicate incorrect polling
parameters such as baud rate or parity.
If the PWR LED does not come on and LA and LB do not flash,
call UP Tech Services at 1-877-874-7378.
If GP105 never comes on, call UP Tech Services at
1-877-874-7378.
General
24 ± 15% VAC (Obtained from the Roof Top Unit)
45 to 65 HZ
Nominal >2 VA
-40 to 160° F (-40 to 70° C) 10 to 95% non-condensing
5.0 x 2.4 x 1.8 in. (128 x 61 x 45.75 cm)
0.2 lb. (0.09 kg)
Processor
Microchip
2048 bytes
1024 bytes w/1,000,000 write cycle capability
Interface
BACnet MS/TP
9.6, 19.2, 38.4, 76.8 kbaud
3-pin screw terminals
Modbus RTU (RS485)
9.6, 19,2 kbaud
6-pin screw terminals
Screened Twisted-Pair (Belden 9272 or 89272)
Controller Status; BACnet; Modbus
MAC Address (1-99), Baud Rate
BacNET Board (Top)