TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R
(5) BV
R
(2) AV
R
(5) BV
R
(5) BV
R/W
(2) AV
R/W
(2) AV
R/W
(2) AV
R
(2) AV
R
(5) BV
R
(2) AV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R/W
(5) BV
R
(5) BV
Johnson Controls Unitary Products
BACnet
Object
Inst
Descriptor
66
E_FREEZE_ST
55
HW_VLV_OUT
2
HYDRONC_HEAT
3
HH_REVER_VLV
62
HYD_S1_SA_SP
63
HYD_S2_SA_SP
80
IO_DVNT_STPT
45
I_C1_ACM_HRS
73
I_COMP1_STAT
46
I_C2_ACM_HRS
76
I_COMP2_STAT
79
I_CFAN_STAT
72
I_FAN_OVER
82
I_FREEZE_1
83
I_FREEZE_2
80
I_GAS_VLVE1
75
I_HPS1
78
I_HPS2
71
I_IFAN_STAT
81
I_LIMIT_1
74
I_LPS1
77
I_LPS2
28
INTELLI-STRT
13
LOADSHED
19
LOW_AMB_OVRD
Default
Min
Max
Point Description
Hot H2O Freeze Thermostat Switch #1
Input Status (1=closed, 0=open/fault)
Hot Water Valve Output Status (0-100%)
Hydronic Heat Enabled
Hydronic Heat Reverse Actuated Valve
Installed
120
80
180
Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
150
80
180
Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
700
0
2000
Indoor/Outdoor Demand Ventilation
Setpoint
Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)
Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)
Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
Intelli-Comfort Gas Valve #1 Input Status
Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
Intelli-Comfort Limit Switch #1 Input Status
Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
Intelli-Start Enabled
Loadshed (0=clear loadshed, 1=set load-
shed operation)
Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)
514067-UAD-A-0509
7