514067-UAD-A-0509
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
BACnet
Read/
Object
Write
Type
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(2) AV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(5) BV
R
(2) AV
R
(2) AV
R
(2) AV
R
(5) BV
R/W
(2) AV
R
(5) BV
R
(2) AV
6
BACnet
Object
Inst
Descriptor
44
E_HPS1
48
E_HPS2
53
E_HPS3
57
E_HPS4
40
E_IFAN_STAT
61
E_LIMIT_ 1
63
E_LIMIT_ 2
65
E_LIMIT_ 3
43
E_LPS1
47
E_LPS2
52
E_LPS3
56
E_LPS4
32
EXH_DAMP_OUT
30
EX_FAN_STAT
10
EX_VFD_INST
32
FRECOOL_STAT
68
HEAT_1_STAT
69
HEAT_2_STAT
70
HEAT_3_STAT
76
H1_ACCUM_HRS
77
H2_ACCUM_HRS
78
H3_ACCUM_HRS
25
HEATING_ENA
27
HGR_HUM_STPT
18
HGR_STAT
47
HGR_VLV_OUT
Default
Min
Max
Point Description
Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
Exhaust Damper Output Status (0-100%)
Exhaust Fan Output Status (0=output is
OFF, 1=output is ON)
Exhaust VFD Installed
Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
Heating #1 Accumulated Run Time
(in hours)
Heating #2 Accumulated Run Time
(in hours)
Heating #3 Accumulated Run Time
(in hours)
Heating Mode Enabled
50
0
100
Hot Gas Reheat Humidity Setpoint (percent
Humidity)
Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
Hot Gas Reheat Valve Output Status
(0-100%)
Johnson Controls Unitary Products