Siemens ISI EN 50295 Brochure page 143

Siemens as-interface brochure
Table of Contents

Advertisement

Overview
Technical specifications
Operating temperature range
• Stationary in °C
• Moving in °C
Color of cores
Flexibility
Behavior in fire
Halogen-free (PVC-free)
Silicone emission free
Ozone and weather resistant
Oil resistance
Smallest permissible bending
radius acc. to DIN VDE 0298,
Part 300, in mm
• Fixed in place
• Flexible
EPDM
TPE
(rubber)
(special PVC compound)
-40 to +85
-40 to +105
-25 to +85
-30 to +105
Brown, blue
Brown, blue
Very Good
Good
flammable
flame-retardant acc. to
IEC 60332-1
VDE 0482 T. 265-2-1
UL 1581 sec. 1061 cable
flame
UL 1581 sec. 1060 CSA
FT1
Yes
No
Yes
Yes
Conditionally resisting
Resisting
Conditionally resisting
Resisting
12
12
24
24
The actuator-sensor interface, the networking system for the low-
est field level, is characterized by easy assembly and installa-
tion. A new connection technique has been specially developed
for the AS-Interface.
The network stations are interconnected via the the AS-Interface
cable. This two-core cable has a trapezoidal profile which pre-
vents polarity reversal.
Connection is made with the cable using the insulation penetra-
tion technique. Blade contacts penetrate the AS-Interface
shaped cable and make reliable contact with the two cores.
Cutting and stripping of cores is not necessary. This technique
allows AS-Interface stations (e.g. I/O modules, intelligent de-
vices) to be connected in the shortest possible time. Devices
can also be replaced in an instant.
The AS-Interface cable is offered in various materials (rubber,
TPE, PUR) to suit applications in a wide range of environmental
conditions (e.g. in an atmosphere saturated with oil particles).
It is also possible to use a round cable for special applications.
In the case of AS-Interface, data and a 24 V DC auxiliary supply
voltage can be connected for the sensors (e.g. BERO proximity
switches) and actuators (e.g. LEDs) via the yellow AS-Interface
cable.
For 24 V DC actuators (e.g. solenoid valves) that have a high
current requirement or that are integrated into EMERGENCY
STOP circuits, the black AS-Interface cable must be used.
TPE special version
acc. to UL Class 2
-30 to + 90
-20 to + 90
Brown, blue
Good
flame-retardant acc. to
IEC 60332-1
VDE 0482 T. 265-2-1
UL 1581 sec. 1061 cable
flame
UL 1685 CSA FT4
No
Yes
Resisting
Resisting
12
24
AS-Interface
Transmission media
AS-Interface shaped cable
PUR
(Polyurethane)
-50 to +90
-50 to +90
Brown, blue
Good
flame-retardant acc. to
IEC 60332-1
VDE 0482 T. 265-2-1
Yes
Yes
Resisting
Resisting
12
24
Siemens IK PI · 2004
6/143
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50295

Table of Contents