AS-Interface
System components and accessories
Repeater/Extender
Design
Repeaters
• Slaves can be used on both sides of the repeater.
• Both sides require an AS-Interface power supply.
• Electrical isolation of the two AS-Interface lines.
Separate display of correct AS-Interface voltage for each side.
• Max. two repeaters may be used in series (max. cable length
300 m).
• Parallel connection of several repeaters is possible
(star configuration possible).
• Installed in user module housing with FK-E coupling module as
bottom part.
6
Repeater connection
Extenders
• Master can be placed at a distance of up to 100 m from the
AS-Interface segment itself.
• Slaves can be used only on side turned away from master.
• AS-Interface power supply only required on side turned away
from master.
• No electrical isolation of the two AS-Interface shaped cable
strands.
• Indication of correct AS-Interface voltage.
• Installed in user module housing with FK-E coupling module as
bottom part.
Extender connection
6/146
Siemens IK PI · 2004
Ordering data
Repeater for AS-Interface
For extending the cable run incor-
porating FK-E coupling module
Extender for AS-Interface
For installation of the master at a
distance incorporating FK-E cou-
pling module
Order No.
6GK1 210-0SA00
6GK1 210-1SA00