Siemens SIPART PS2 6DR50xx Manual page 137

Electropneumatic positioner for linear and part-turn actuators
Table of Contents

Advertisement

Fault indication
(symptoms)
SIPART PS2 stops during
"RUN 1".
SIPART PS2 stops during
"RUN 2".
SIPART PS2 stops during
"RUN 3".
SIPART PS2 stops during
"RUN 5"and does not reach
"FINISH" (delay time:
> 5 min).
Table 5
Fault indication
(symptoms)
For SIPART PS2, "CPU
test" flashes in the display
(approx. every 2 sec).
Piezo valve(s) do(es) not
switch.
In manual or automatic
mode, the actuator cannot
be moved or only in one
direction.
Piezo valve(s) do(es) not
switch (no quiet "clicking"
can be heard when the + or
– button is pressed in
button is pressed in
manual mode).
Table 6
SIPART PS2 Manual
A5E00074631--06
possible cause(s)
Initialization started from end
position and
reaction time of max. 1 min.
not waited for.
Mains pressure not connected
or insufficient.
Transmission ratio selector and
parameter 2 (YAGL) as well as
actual stroke do not match.
Stroke not correctly set for
lever.
Piezo valve(s) do(es) not
switch (see table 6).
Actuating time too high.
"Batches" (play) in the
positioner -- actuator -- control
valve system
possible cause(s)
Water in the pneumatic block
(due to wet compressed air)
Moisture in the pneumatic
block
Screw between shrouding
cover and pneumatic block not
tightened firmly or cover
jammed.
Dirt (chips, particles) in the
pneumatic block
Deposits on contact(s)
between electronics board and
pneumatic block can develop
due to abrasion as a result of
continuous high vibration
stress.
Operation
Remedies
Up to 1 min. delay time
required.
Do not start initialization from
end position.
Secure the mains pressure.
Check settings:
see leaflet: figure "device view
(7)" as well as parameters 2
and 3
Check stroke setting at lever.
see table 2
Open reactor completely
and/or set PZ pressure (1) to
maximum permissible value.
If necessary, use booster.
Part-turn actuator:
Check if set screw of the
coupling wheel is inserted
firmly
Linear actuator:
Check if lever is connected
firmly to positioning shaft.
Eliminate any other play
between actuator and control
valve.
Remedies
At an early stage, this fault can
be eliminated by subsequent
operation with dry air (if ne-
cessary, in the temperature
cabinet at 50 to 70°C).
Otherwise: Repair
(see chapter 5, page 145)
Tighten screw, if necessary
eliminate jam.
Repair (see chapter 5,
page 145) or new device;
integrated fine screen,
also replace and clean.
Clean all contact surfaces with
spirit; if necessary, re-bend the
pneumatic block springs
slightly.
137