Messages on exiting configuration mode:
4.nn.nn
x
VER
x
Error
x
SLnn
x
Messages during operation:
CPU
x
START
x
HW /
x
ERROR
NOINI
x
nnn.n
x
AUTnn
x
MANnn
oFL / 127.9
x
EXSTP
x
EX UP
x
EXDWN
x
EXTPSt
InPSt
HTCNF
x
142
Meaning/cause
Software version
Monotony violation of the
free characteristic curve at
vertice n
Meaning/cause
Message after applying the
electrical power supply
Hardware error
x
Positioner is not initialized
x
x
Actual position [in %] with
initialized positioner. Flashing
decimal point indicates com-
munication with a class 2
master
x
Automatic mode
(nn = setpoint)
x
Manual mode (nn = setpoint)
x
x
Display range was exceeded.
Possible causes:
friction clutch or
S
transmission ratio selector
S
were misadjusted or
positioner was fitted on
S
another actuator without
re-initialization.
x
Actuator was stopped via
binary input
x
Actuator is moved to the
upper stop via binary input
x
Actuator is moved to the
lower stop via binary input
Partial stroke test was
activated e.g. via binary input
cyclic partial stroke test
x
x
x
HARD configuration running
Measure
Wait
S
Correct value
S
Measure
Wait
S
Replace electronics
S
Start initialization
S
Press operating mode
S
button to switch to
automatic mode
Adjust friction clutch in
S
such a way that the
indication of the actual
value remains between
0.0 and 100.0 on
moving the actuator or
switch over the
S
transmission ratio
selector or
set to the factory setting
S
(preset) and initialize