Operation
Fault indication
(symptoms)
Actuator does not move
Piezo valve(s) do(es) not
switch (quiet "clicking" can
be heard however when
the + or
the + or – button is pressed
button is pressed
in manual mode).
A piezo valve switches
continuously in stationary
automatic mode (constant
setpoint) and in manual
mode.
Table 7
Fault indication
(symptoms)
Both piezo valves switch
continuously and
alternately in stationary
automatic mode (constant
automatic mode (constant
setpoint) and in manual
mode, actuator oscillates
around a mean value.
SIPART PS 2 does not
"drive" control valve up to
the stop (at 20 mA).
Table 8
138
possible cause(s)
Compressed air < 1.4 bar
Reactor valve(s) closed
(screw(s) at the right-hand
stop)
Dirt in the pneumatic block
Pneumatic leakage in the
positioner – actuator system
Start leakage test in "RUN 3"
(initialization)!!!
Dirt in the pneumatic block
(see above)
possible cause(s)
Too much slipstick of stuffing
box of control valve or actuator
Batches (play) in the positioner
-- actuator – control valve
system
Actuator too fast
Supply pressure too low.
Load of the feeding controller
or system output is too low.
Remedies
Set supply air pressure to
> 1.4 bar.
Open reactor screw(s) (see
leaflet, figure "device view (6)"
by turning it/them
anti-clockwise.
Repair (see chapter 5,
page 145) or new device;
integrated fine screen,
also replace and clean.
Eliminate leakage in the
actuator and/or supply line
If the actuator is intact and the
supply line is leak-tight:
Repair (see chapter 5,
page 145) or new device
see above
Remedies
Reduce slipstick or increase
dead zone of SIPART PS 2
(dEbA parameter) until
oscillation stops.
Part--turn actuator:
Check if set screw of the
coupling wheel is inserted
firmly
Linear actuator:
Check if lever is connected
firmly to positioning shaft.
Eliminate any other play
between actuator and control
valve.
Increase actuating times via
reactor screws.
If fast actuating time is
required, increase dead zone
(dEBA parameter) until
oscillation stops.
Increase supply pressure
Interconnect load converter
Select 3/4 transmitter
operation
SIPART PS2 Manual
A5E00074631--06