Siemens SIPART PS2 6DR50xx Manual page 133

Electropneumatic positioner for linear and part-turn actuators
Table of Contents

Advertisement

Error
three-
Event
code
level
12
yes
Slipstick effect
occurs
13
yes
Temperature
short of
14
yes
Temperature
exceeded
15
yes
Position average
deviates from the
reference value
Table 4-2
Events that can activate the fault message output
Explanations for the "Error codes" column:
1
2
3
SIPART PS2 Manual
A5E00074631--06
Parameter-
setting
d. STIC¸OFF
H. TMIN¸OFF
J. TMAX¸OFF
P. PAVG¸OFF
Control deviation monitoring
In automatic mode, the deviation between the setpoint and actual value
is monitored continuously. According to the setting of parameter
48. TIM, the monitoring time for setting the fault messages, and
49. LIM, the response threshold of the fault message, the fault
message is activated if the control deviation remains. As soon as the
control deviation falls below the response threshold again, the fault
message is cancelled.
Automatic mode monitoring
If parameter "47. FCT", the fault message output function, is set
accordingly, a fault message is generated if the device is not in
automatic mode. In this way, e.g. the control system can be warned if
the device was switched to manual mode or configuration on location.
Binary input BE1 or BE2 active
If parameter "47. FCT", the fault message output function, and
parameter "42.BIN1", the binary input 1 function, are set accordingly,
a fault message is generated when the binary input is activated. This
can be e.g. a stuffing box monitoring switch, a temperature switch or a
limit switch (e.g. for pressure).
Binary input 2 (for the alarm unit option) can be configured in the same
way.
Error message
Possible
disappears if...
causes
... no more slipstick
Increased slipstick,
can be detected,
valve no longer
or the function is
moves constantly but
deactivated.
judders instead
... the lower tem-
Ambient temperature
perature threshold
too low
values are no longer
fallen short of.
... the upper tem-
Ambient temperature
perature thresholds
too high
are no longer
exceeded.
... after a comparison
In the last comparison
interval, a position
interval, the valve
average is calculated
trajectory changed so
that is within the
much that a deviating
reference value
position average was
thresholds or the
calculated.
function is
deactivated.
Operation
133