15. Commissioning Cont.
sequence P01 alternates with -- -- --).
Figure 15.23
• Press the reset button 6, in Figure 15.21,
to scroll the various parameters until
reaching the valid parameter P15 for
appear on the LCD display (the sequence
P15 alternates with 00).
Figure 15.24
• Set the value by turning knob 8 in Figure
15.21 from a minimum of 30 (the sequence
P15 alternates with 30)
Figure 15.25
to a maximum of 255 based on the
RIVA ADVANCE COMBI MANUAL
15.20.
90
1
30
0,5
00
0
LCD Value
Figure 15.26
• Once the desired value is set, the
that it was stored occurs
automatically, after 5 seconds, with OK
appearing on the LCD display.
Figure 15.27
• To exit programming, position the function
selector/heating temperature adjustment
knob 7 as shown in Figure 15.28.
8
Figure 15.28
Knob 7 must be positioned as shown in
Figure 15.29 to respect the trend of the
delivery temperature with respect to the set
Figure
140
182
200
1,5
2
3
218
4
6
255
Coeff. K
Setting No.
7
6
50