Technical Data - Theben MIX 2 Series Manual

Table of Contents

Advertisement

MIX 2 series RMG 4 U / RME 4 U actuators

4 Technical data

KNX operating voltage
Operating voltage
Frequency
Standby output
Type of installation
Width
Connection type
Max. cable cross-section
Number of channels
Contact gap
Voltage output
Switch output
Switching of different phases
Type of contact
Resistive load
Incandescent and halogen lamp load
Fluorescent lamp load (KVG)
parallel-corrected
Fluorescent lamp load (KVG) not
corrected
Fluorescent lamp load (EB)
Energy-saving lamps
LED lamps
Suitable for SELV
Ambient temperature
Protection rating
Protection class
Updated: Apr-15 (Subject to changes)
Bus voltage, ≤ 4 mA
110 – 240 V AC
50 – 60 Hz
0.3 W
DIN-rail
4 TE
KNX bus terminal
Solid: 0.5 mm² (Ø 0.8) to 4 mm² | strand with
crimp terminal: 0.5 mm² to 2.5 mm²
4
< 3 mm
240 V AC
Floating
Possible
16 A, 3 A NO contact
3680 W
2000 W
1300 W (140 μF)
2000 VA
1200 W
300 W
< 2 W = 55 W or > 2 W < 8 W = 180 W
Yes, if all channels switch SELV
-5 °C ... +45 °C
IP 20
II in accordance with EN 60 730-1