Section 1
General Information
Analog Outputs
From Microprocessor
From Microprocessor
MN722
Two programmable analog outputs are provided on J1-6 and J1-7. See Figure 3-22.
These outputs are scaled 0 - 5 VDC (1mA maximum output current) and can be used to
provide real-time status of various control conditions. The output conditions are defined
Table NO TAG
in
of Section 4 of this manual.
The return for these outputs is J1-1 analog ground. Each output is programmed in the
Level 1 Output block.
1.
Connect the Output #1 wires to J1-6 and J1-1.
2.
Connect the Output #2 wires to J1-7 and J1-1.
Figure 3-22 Analog Outputs Equivalent Circuits
10K
+
10K
.033 mf
10K
+
10K
.033 mf
J1
1
50
6
Notes:
+
50
7
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
All OP Amps are TL082 or TL084
Analog Ground is separated from
Chassis Ground. Electrically they
are separated by an RC network.
Receiving & Installation 3-43