Control units
(cont.)
5 8

EA1 extension

Part no. 7452091
Function extension inside enclosure for wall mounting.
Using the inputs and outputs allows up to 5 functions to be
achieved:
1 switching output (floating changeover contact)
■ Central fault message output
■ Switching a feed pump to a substation
■ Switching the DHW circulation pump (only with Vitotronic 200, type
HO1B and HO2C)
1 analogue input (0 to 10 V)
■ Specifying set boiler water temperature
3 digital inputs
■ External operating mode changeover for 1 to 3 heating circuits
(only with Vitotronic 200, type HO1B and HO2C)
■ External blocking
■ External blocking with central fault message
■ Minimum boiler water temperature demand
■ Fault messages
■ Brief operation of DHW circulation pump (only with Vitotronic 200,
type HO1B and HO2C)
Power supply for DHW circulation pump
DHW circulation pumps with their own internal control unit must be
6
connected to a separate power supply. Mains connection via the
Vitotronic control unit or Vitotronic accessories is not permissible.
5 8
VIESMANN
92
0
1 8
0
1 8
Specification
Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
4 A
Power consumption
4 W
Rated relay output break-
2(1) A, 250 V~ each, total max. 4 A~
ing capacity
Safety category
I
IP rating
IP 20 D to EN 60529, ensure through
design/installation
Permissible ambient temperature
– Operation
0 to +40 °C
Installation in living spaces or boiler
rooms (standard ambient conditions)
– Storage and transport
–20 to +65 °C
Specification
Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
2 A
Power consumption
4 W
Rated breaking capacity
2(1) A, 250 V~
of the relay output
Safety category
I
IP rating
IP 20 D to EN 60529, ensure through
design/installation
Permissible ambient temperature
– Operation
0 to +40 °C
Installation in living spaces or boiler
rooms (standard ambient conditions)
– Storage and transport
–20 to +65 °C