Control units
(cont.)
Cylinder temperature sensor
For Vitodens with loading cylinder or solar cylinder also an additional
outlet temperature sensor.
These sensors are connected to the control unit and built into the
boiler or cylinder.
Specification
IP rating
Sensor type

Specification Vitotronic 100, type HC1B

Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
6 A
Protection class
I
Function type
Type 1 B to EN 60730-1
Permissible ambient temperature
– During operation
0 to +40 °C
Installation in living spaces or boiler rooms
(standard ambient conditions)
– During storage
and transport
–20 to +65 °C
6.2 Vitotronic 200, type HO2C, for weather-compensated operation
Design and functions
Modular design
The control unit is integrated into the boiler.
The control unit comprises a standard unit, electronics modules and
a programming unit with 5-inch colour touchscreen.
Standard unit:
■ ON/OFF switch
■ Optolink laptop interface
■ Only for Vitodens 333-F and 343-F: LAN interface
E.g. for remote control of the heating system by the Vitotrol Plus
app (operating system iOS 7.0 or Android 4.0).
■ Operating and fault display
■ Reset button
■ Fuses
Programming unit:
■ Easy operation thanks to:
– Colour touchscreen with plain text and graphic display
– Large font and colour depiction for good contrast
– Context-sensitive help
■ With digital time switch
VITODENS
IP 32
Viessmann NTC 10 kΩ at
25 ºC
Permissible ambient temperature
– During operation
– During storage and transport
Electronic tempera-
ture limiter setting
(heating mode)
82 °C (change not possible)
DHW temperature setting range
– Vitodens with
loading cylinder
10 to 63 °C
– Vitodens with
DHW cylinder
with internal indi-
rect coil
10 to 68 °C
■ Setting:
– Room temperature
– Reduced room temperature
– DHW temperature
– Operating program
– Time programs for central heating, DHW heating and DHW cir-
culation
– Economy mode (ECO)
– Comfort mode
– Holiday program
– Heating curves
– Favourites menu
– Parameters with plain text display
– Actuator tests
– Test mode
■ Display:
– Boiler water temperature
– DHW temperature
– Energy cockpit with indication of:
– Energy yields
– Energy consumption
– Operating data
– Diagnostic details
– Fault messages
0 to +90 °C
–20 to +70 °C
VIESMANN
79
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

B2ubB2sbB2tb

Table of Contents