External Extension; Ea1 Extension - Viessmann Vitoladens 300-C Installation And Service Instructions Manual

Oil condensing boiler with integral boiler control unit
Hide thumbs Also See for Vitoladens 300-C:
Table of Contents

Advertisement

External extension

EA1 extension

Fig. 67
F1
Fuse
DE1
Digital input 1
DE2
Digital input 2
DE3
Digital input 3
0
10 V 0
10 V input
Power supply
Digital data inputs DE1 to DE3
The following functions can alternatively be connected:
External operating program changeover for each
heating circuit
External blocking
External blocking with fault message input
External demand with minimum boiler water temper-
ature
Fault message input
Brief operation of the DHW circulation pump
External contacts must be floating. When connecting
external contacts, observe the requirements of protec-
tion class II: 8.0 mm air and creep path or 2.0 mm
insulation thickness to live parts.
A
Power supply for additional accessories
Central fault message/feed pump/DHW circu-
aBJ
lation pump (potential-free)
Connect DHW circulation pumps with stand-
alone functions directly to the 230 V
KM-BUS
aVG
Input function assignment
Select the input functions via the parameter changes/
codes in the "General" group at the boiler control unit:
DE1: Parameter/coding address 3A
DE2: Parameter/coding address 3b
DE3: Parameter/coding address 3C
Assigning the operating program changeover
function to the heating circuits
Select the operating program changeover function for
the relevant heating circuit via parameter/coding
address d8 in the "Heating circuit" group at the boiler
control unit:
Changeover via input DE1: Parameter/code d8:1
Changeover via input DE2: Parameter/code d8:2
Changeover via input DE3: Parameter/code d8:3
Function description
supply.
91