Ea1 Extension - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

External extensions (accessories)

EA1 extension

Fig. 69
F1
Fuse
DE1
Digital input 1
DE2
Digital input 2
DE3
Digital input 3
0
10 V 0
10 V input
Power supply
Digital data inputs DE1 to DE3
The following functions can alternatively be connected:
External operating program changeover for each
heating circuit
External blocking
External blocking with fault message input
External demand with minimum boiler water temper-
ature
Fault message input
Brief operation of the DHW circulation pump
External contacts must be floating. When connecting
external contacts, observe the requirements of protec-
tion class II: 8.0 mm air and creep path or 2.0 mm
insulation thickness to live parts.
(cont.)
A
Power supply for additional accessories
Central fault message/feed pump/DHW circu-
aBJ
lation pump (potential-free)
Connect DHW circulation pumps with stand-
alone functions directly to the 230 V
KM-BUS
aVG
Input function assignment
Select the input functions via the parameter changes/
codes in the "General" group at the boiler control unit:
DE1: Parameter/coding address 3A
DE2: Parameter/coding address 3b
DE3: Parameter/coding address 3C
Assigning the operating program changeover
function to the heating circuits
Select the operating program changeover function for
the relevant heating circuit via parameter/coding
address d8 in the "Heating circuit" group at the boiler
control unit:
Changeover via input DE1: Parameter/code d8:1
Changeover via input DE2: Parameter/code d8:2
Changeover via input DE3: Parameter/code d8:3
Function description
supply.