3.9.4 BIN Status of binary input and outputs

This menu indicates the respective status of the binary input and outputs.
BI1
Status of binary input BI1 on/oFF
g
BO1
Status of binary output BO1 on/oFF
g
BO2
Status of binary output BO2 on/oFF
g

3.9.5 ADJ Adjusting the analog inputs and output

This function enables you to adjust zero and span for the analog inputs and the analog output.
Proceed as follows:
You are in the main group I-O and have selected ADJ.
1. Press the enter key. ADJ IN1 is displayed.
2. Select the respective input or output using the cursor keys:
AdJ IN1
Adjust analog input IN1
AdJ IN2
Adjust analog input IN2
AdJ Y1
Adjust analog output Y
3. Press the enter key.
4. You are prompted to enter the key number. Enter the key number via the cursor keys.
5. Confirm with the enter key.
6. Adjust the desired signal to the lower range value using a high-precision meter. In the
adjustment section of the display, ZERO and IN1 (IN2 or Y1) are displayed alternately.
7. Press the enter key. Zero adjustment is completed. The display shows 0.0 and ZERO.
8. Adjust the desired signal to the upper range value using a high-precision meter. In the
adjustment section of the display, SPAN and IN1 (IN2 or Y1) are displayed alternately.
9. Press the enter key. Span adjustment is completed. The display stops blinking and shows
100.0 and SPAN.
10. Press the return key once. Continue with step 2 if you wish to adjust additional inputs or
the output. The key number does not need to be entered again.