Functions of the compact controller
Note!
When values exceed or fall below the measuring range, Y1K1 only becomes effective when
the compact controller is in automatic mode.
The parameter Y1K1 can also be set in the main group OUT via the SAFE function as well as in
the main group AUX via the RE.CO function (see sections 3.5.1 and 3.7.1).

3.2.5 CLAS Assignment of X and WE

Internally, the compact controller operates with the analog input signals X and WE. The CLAS
function is used to assign these signals to the analog inputs IN1 or IN2. By default, X is assigned
to analog input IN2 and WE to analog input IN1.
Assignment of X
IN1 X
X assigned to analog input IN1
g
IN2 X
X assigned to analog input IN2
g
Assignment of WE
IN1 WE
WE assigned to analog input IN1
g
IN2 WE
WE assigned to analog input IN2
g

3.2.6 DI.FI Filtering of input variable X and WE

This function enables you to determine whether X and/or WE are to be filtered.
The first-order filter (low-pass filter or Pt1 behavior) smooths the selected signals and suppresses
input signal interferences of higher frequency.
The time constant of the Pt1 element is defined by the parameter TS.X for the input signal X, and
by TS.WE for the input signal WE. The time constant is given in seconds.
Filtering of input variable X
oFF X
Filtering of input variable X deactivated
g
on X
Filtering of input variable X activated
g
Filtering of input variable WE
oFF WE
Filtering of input variable WE deactivated
g
on WE
Filtering of input variable WE activated
g
22
EB 6493-1 EN