7. COMMUNICATION THAT DO NOT REQUIRE
THE SEQUENCE PROGRAM
7.2.10
Use the SetValue to set the parameter in the AJ71PB96F/A1SJ71PB96F from the client.
[Parameters required by the client]
• Variable Identifier
• Desired Value
[Server (AJ71PB96F/A1SJ71PB96F) answer parameters]
None
Bus parameter setting (SetValue: Server)
Set the parameter type to be set as shown in the following table.
Set the value as shown in the following table.
Vriable Identifier
6
Tsl
7
Min Tsdr
8
Max Tsdr
9
Tqui
10
Tset
11
Ttr
12
G
13
In Ring Desired
15
Max Retry Limit
Slot time 37 to 16383
Minimum response delay time 11 to 1023
Maximum response delay time 37 to 1023
Quiet time 0 to 127
Setup time 0 to 255
Target token rotation time 256 to 16777215
Gap update rate 1 to 100
Not specified by the A1SJ71PB96F
Maximum retry count 0 to 7.
7-38
MELSEC-A
Current Value