Program, Parameter, Comment, Device, And Buffer Memory Download Termination (Terminatedownloadsegument: Server) - Mitsubishi Electric A1SJ71PB96F User Manual

Melsec a series, profibus modules, a(1s)j71pb96f
Table of Contents

Advertisement

7. COMMUNICATION THAT DO NOT REQUIRE
THE SEQUENCE PROGRAM
7.1.15
When the MoreFollows parameter of the DownloadSegument.response is False, or the data received
using DownloadSegument.response was not correctly written into the PC CPU, a
TerminationDownloadSegument is transmitted from the AJ71PB96F/A1SJ71PB96F.
[Server (AJ71PB96F/A1SJ71PB96F) answer parameters]
• Access Specification
• Final Result
Explanation
When the Final Result is False, then is can be suspected that data that exceeds the capacity set
by the PC CPU parameter was sent or that an error occurred in the PC CPU.
Also, in this case the domain data was only partially written. Redownload or rewrite using the PC
peripheral equipment.
[Parameters required by the client]
None
Program, parameter, comment, device, and buffer memory download
termination (TerminateDownloadSegument: Server)
The Index or Name of the domain specified by InitiateDownloadSequence is specified.
Access Specification
Index
Variable Name
Final Result
False = 0
True = FFh
Setting value
Domain Index
Domain Name
Meaning
An error occurred during the download.
The download terminated normally.
7-19