4. FUNCTIONS
4.7.2
The AJ71PB96F/A1SJ71PB96F network trouble information can be obtained when the PC CPU refers
to this area. The area configuration, detailed code, and counter measures are shown below.
(decimal)
(1) When the trouble type is 100h (initialization trouble):
Code 1 in type
4h
Ah
Bh
Ch
Other

Network trouble information area

Adress
1376
1377
1378
1379
Reserved
1407
Code 2 in type
Initialization
FMS/FMA7
phase
error code
FFFFh
Other than
FFFFh
Other than
FFFFh
Other than
FFFFh
Trouble type
Code 1 in type
Code 2 in type
*1
The latest trouble information is given the
smallest No., and a maximum of 8 trouble
information can be displayed.
The old information is moved in numerical
order downwards.
*1 x 7
Description
There is an error with the remote
OD setting information.
There is an error with the local OD
setting information.
There is an error with the bus
parameter setting information.
There is an error with the CRL
setting information.
There is an error in the module.
4-21
MELSEC-A
Counter measure
Correctly set the remote OD.
Correctly set the local OD.
Correctly set the bus parameter
information.
Correctly set the CRL.
Contact Mitsubishi Electric.