Communications Parameters - Omron E5CC Communications Manual

Digital temperature controllers. e5*c series
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

1 Communications Methods
1-1-6

Communications Parameters

The E5@C's communications specifications are set in the communications setting level. These param-
eters are set on the E5@C's front panel. The following table shows the communications parameters and
their setting ranges.
Item
Communications protocol
setting
Communications unit number
Communications baud rate
Communications data length *
Communications stop bits *
Communications parity
Send data wait time
Highlighted values indicate default settings.
*
When the Protocol Setting parameter is set to Modbus, the communications data length must be 8 bits, and
the communications stop bits must be 1 bit by setting the communications parity to Even/Odd or it must be 2
bits by setting the parity to None. These two parameters are not displayed on the Controller's display.
1 - 8
Code
Settings
CompoWay/F /Modbus
psel
0 to 99
u-no
9.6/19.2/38. 4/57.6 (kbit/s)
bps
7/8 (bit)
len
1/2
sbit
None, Even, Odd
prty
0 to 99
sdwt
E5@C Digital Temperature Controllers Communications Manual (H175)
Set Values
cwf/mod
0, 1 to 99
9.6/19.2 /38.4/57.6 (kbit/s)
7/8 (bit)
1/2
none/eVen/odd
0 to 99 ms, default time: 20 ms