■ Communications Parameters

Item
Communications protocol
Communications unit number
Communications baud rate
Communications data length
(See note.)
Communications stop bits
Communications parity
Send data wait time
● Communications Parameter Setup
Cable Diagram
The E5CN/AN/EN/GN's communications specifications are set in the
communications setting level. These parameters are set on the E5CN/
AN/EN/GN's front panel. The following table shows the communications
parameters and their setting ranges.
Code
Settings
psel
CompoWay/F (SYSWAY)/Mod-
bus
u-no
0 to 99
bps
1.2/2.4/4.8/9.6/19.2/38.4/57.6
(kbit/s)
len
7/8 (bit)
sbit
1/2
prty
None, Even, Odd
sdwt
0 to 99
Note: The communications data length for Modbus must be 8 bits.
Before you carry out communications with the E5CN/AN/EN/GN, set up
the communications unit number, baud rate, and other parameters by
carrying out the following procedure. For details on operations other
than communications parameter setup, refer to the E5CN/E5AN/E5EN/
E5GN Digital Temperature Controllers User's Manual Basic Type (Cat.
No. H156) for the devices being used.
1.
Press the O Key for at least three seconds to move from the
"operation level" to the "initial setting level."
2.
Press the O Key for less than one second to move from the "initial
setting level" to the "communications setting level."
3.
Select the parameters as shown below by pressing the M Key.
1.1 Overview of Communications Methods
Cross-sectional area of
conductor
2
AWG24: 0.205 mm
2
AWG14: 2.081 mm
Set Values
cwf
/mod
1
0,
to 99
1.2/2.4/4.8/
(kbit/s)
/8 (bit)
7
1/
2
none/
even
0 to 99 ms, default time:
Highlighted values indicate default settings.
9.6
/19.2/38.4/57.6
/odd
20
ms
1-7