6 Programless Communications
With the default settings, the following parameters are set for the upload areas.
Check the values in the upload areas to see if they are the same as those that are given in
the following table. (It is not necessary to check address for which "---" is given in the Value
column.)
No.0
DM0
DM30
DM1
DM31
DM2
DM32
DM3
DM33
DM4
DM34
DM5
DM35
DM6
DM36
DM7
DM37
DM8
DM38
DM9
DM39
DM10
DM40
DM11
DM41
· · ·
· · ·
DM13
DM43
DM14
DM44
*
If the default settings are used and a sensor is not connected, the PV display on the E5CC will show an input
error (s.err) and the process value in the upload area will be 1320 (528 hex).
 Changing E5CC Settings
(1) We will check the area that is used to change E5CC set values.
The area that is used to change the set value is called the download area.
DM15 to DM29 is the download area for the No. 0 Controller, DM45 to DM59 is the
download area for the No. 1 Controller, and DM75 to DM89 is the download area for the
No. 2 Controller.
6 - 90
No.1
No.2
DM60
Response Flag (fixed)
DM61
Communications Status (fixed)
DM62
Communications Monitor
Parameter
DM63
Status (Upper Word)
DM64
Status (Lower Word)
DM65
Status 2 (Upper Word)
DM66
Decimal Point Monitor
DM67
Process Value
DM68
Internal Set Point
DM69
Heater Current 1 Value Monitor
DM70
MV Monitor (Heating)
DM71
Not used.
· · ·
· · ·
DM73
Not used.
DM74
Do not use (reserved).
Parameter
0
Alternates between 0 and 1.
---
---
---
---
---
Process Value
---
---
---
---
· · ·
---
---
E5@C Digital Temperature Controllers Communications Manual (H175)