6-6-4

E5@C Controller Setup

Set up programless communications. Perform the procedure that is given in 6-4-4 E5
Setup.
6-6-5

Checking Operation

The SP and RUN/STOP status of the E5@C Controllers will be changed to check operation. Make sure
that this will not create any problems in the controlled system.
You cannot use the memory for CJ-series Units (e.g., in the DM or EM Area) in NX-series or NJ-series
PLCs for monitoring directly in the program in the PLC. Therefore, to monitor the memory for CJ-series
Units used in programless communications, you must allocate variables.
 Checking E5C Monitor Values
(1) Change to Offline Mode to enable changing the product on the Sysmac Studio.
Select Controller
(2) Create variables on the Sysmac Studio to check the values of E5CC parameters.
(a) Double-click Global Variables under Programming
(b) Create a variable.
If you name this variable D00X here, you can use D000 to D089 allocated in the upload
area and download area for programless communications as array variable D00X[0] to
D00X[89] in the user program in the PLC.
E5@C Digital Temperature Controllers Communications Manual (H175)
Offline from the menu bar.
Right-click in the global variable table and select Create New.
Enter ARRAY[0..89]OF WORD in the Data Type column and %D0 in the AT column.
Select the check box in the Retain column.
6 Programless Communications
Data.
@
C Controller
6
6 - 43