6-2
E5C Setup
The parameters that are used for programless communications are shown with a gray background in
the following diagram. These parameters will be displayed if you set the Protocol Setting parameter to
fins, mcp4, or fxp4. (Some of the parameters are always displayed.) The parameters in the commu-
nications setting level are described first, followed by those in the adjustment level.
Power ON
Operation Level
Press O Key for
at least 3 s.
Initial Setting Level
in-t
*
These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
6-2-1

Protocol Setting

Set the Protocol Setting parameter to fins to connect to an OMRON PLC, mcp4 to connect to a Mit-
subishi Q-series or L-series PLC, fxp4 to connect to a Mitsubishi FX-series or Keyence KV-series
PLC, and cmp to use component communications. Refer to 6-1-5 Connectable PLCs for lists of the
PLCs that can be connected.
Refer to 7-1 Component Communications for information on component communications.
Communications Setting Level
Display condition: None
Parameter name

Protocol Setting

*
Selection is possible only for E5@C version 2.1 or later.
E5@C Digital Temperature Controllers Communications Manual (H175)
Adjustment Level
Press O Key for
less than 1 s.
l.adj
1234
M
25
at
0
off
M
cmwt
on
M
Press O Key for
at least 1 s.
Communications Setting Level
Press O Key for
less than 1 s.
psel
fins
M
u-no
5
0
M
bps
57.6
M
sdwt
20
M
maxu
0
M
Displayed characters
psel
6 Programless Communications
Adjustment Level
w8of
Work Bit 8 OFF Delay
Display
0
M
plcm
AT Execute/Cancel
Communications
Monitor
0
M
Communications
Writing
*
Protocol Setting
*
area
Area
0
M
adrh
Communications
First Address Upper
Word
Unit No.
*
0
M
adrl
Communications
First Address Lower
Word
Baud Rate
*
0
M
rwat
Send Data Wait
Receive Data Wait
Time
Time
*
1000
M
Highest
unit
Communications
Communications
Node Number
0
Unit No.
M
Setting range
cwf: CompoWay/F
mod: ModbusRTU
cmp: Component communications
fins: Host Link (FINS)
mcp4: MC protocol (format 4)
fxp4: Dedicated protocol (format 4)*
up 1
Upload Setting 1
1
M
up 2
Upload Setting 2
2
M
dn 1
Download Setting 1
31
M
dn 2
Download Setting 2
61
M
copy
Copy
off
M
Default
cwf
6
6 - 7