Final checks
Final check of the permissible energies and forces.
Risk of injury due to moving mechanical parts
Check permissible forces and energies after the door drive has been commissioned in the
complete system and adjust them if they exceed their limit values.
Please observe the valid applicable standards and directives for the respective application,
as well as the following guidelines:
• Gearing up or down is not allowed on the toothed belt because this would change the
Risk of injury and material damage due to excessive closing or opening force of the door
Exceeding the maximum static closing and opening force may lead to personal injuries or
damage to the door drive and to mechanical components of the door.
The maximum static closing and opening forces at the closing edge without additional
protective equipment must not exceed 150 N (according to EN81-20, 150 N only applies to
glass and folding doors in the opening direction)!
Door control units SIDOOR AT40 and ATD400V for elevators
System Manual, 06/2018, A5E42192709-AC
WARNING
kinetic energies or static forces on the door. The door width would then no longer be
valid.
WARNING
Connecting and commissioning
8.6 Final settings and checks
133