☆: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Settings
Battery Settings
Dry Contact
Identification
Type
Serial Number
Firmware Version
Memorandum
Log
Fault Log
Shutdown Log
AC input Log
Reset All Log Data
Note 1: Refer to "9-4 Input voltage sensitivity settings".
Note 2: Refer to "9-3 Battery life".
Note 3: BMS stands for Battery Management System.
A lead battery UPS does not require the BMS.
A lithium battery UPS always are safely managed a battery condition using the
BMS.
BL50T/BL75T/BL100T
Menu item
Description
Set the level at which a low battery warning
Low Battery Warning☆
can be detected.
BMS setting (Note 3)
Temporarily stop communication between
the CPU in the battery pack (BMS) and the
CPU in the CPU when replacing the
battery.
BSsignal
Set the condition for BS signal reception.
ValidRange☆
BSsignal
Set the delay time for a BS signal.
Delay Time
BUsignal
Set the delay time for a BU signal.
Delay Time
Dry Contact Logic
Set the dry contact logic.
Remote ON/OFF
Set the remote signal logic.
This setting is common to a contact signal
Logic☆
I/O card and remote ON/OFF dedicated
connector.
Display the names of the UPS and battery
pack.
Display the serial number of the UPS.
Display the firmware version of the UPS.
Information up to 20 alphanumeric
characters can be viewed.
Display up to 10 logs of faults that occurred
in the past (time of occurrence and fault
details).
Display up to 10 reasons for UPS
shutdown.
Display up to 10 logs of events that
occurred in the past.
Clear each piece of log data.
3 Check and start the operation
3-4Operation by using the LCD menu
Value
Low battery warning:
Initial setting (factory default), Level
change: 0 to 100%
BMS mode enabled/disabled
(Factory default) Enabled
BS signal valid range:
Always enabled (factory default),
Only for backup operation
BS signal delay time:
0 to 9000 seconds, or 9999 seconds
(Factory default: 0 second)
BU signal delay time:
0 to 180 seconds
(Factory default: 0 second)
Dry Contact logic:
BU, BL, TR, WB:
Normal (factory default)/
Reverse
Remote ON/OFF logic:
OFF when short-circuited (factory default),
OFF when opened, Disabled
Type name:
UPS: Model.
Battery: Model
Serial number:
S/N: xxxxxxxxxxxxxxxG
Firmware version:
UPS: M:x.xx
USB: S:x.xx
-
Fault log:
Year/month/day/hour/minute, message
Shutdown log:
Year/month/day/hour/minute, message
AC input log:
Year/month/day/hour/minute, message
Execute Reset All Log Data
Menu Type
Advanced
Standard
Advanced
Standard
3
45