Omron BL50T Instruction Manual page 32

Uninterruptible power supply
Table of Contents

Advertisement

3 Names and functions of parts in the operation and display sections
3-1 Names and functions of parts in the operation and display sections
■ Operation while the UPS is in use or AC input error
UPS status
UPS event
■ Battery error
UPS status
Battery
deterioration
Battery end
of life
Battery
temperature
error (charge
stop)
No battery
connection
Note 2: The power output is different depending on the operating condition.
Note 3: In power recovery immediately after backup operation ends, in rare cases, self-heating might occur in the
Note 4: Different depending on the operating condition.
32
LED
Icon
Buzzer
None
LED
Icon
Buzzer
Intermitte
nt, at
intervals
(Note 4)
of 2
seconds
(Flashing)
Intermitte
nt, at
intervals
(Note 2)
of 4
seconds
(Flashing)
Intermitte
nt, at
intervals
of 2
seconds
(Flashing)
battery, activating the protection function, and the error (Fault-E12) might be displayed.
In that case, the commercial power is output as-is (charging stopped).
Then, the battery temperature drops, the error display is automatically canceled, and the charging
operation resumes.
Message at
Output Charge
top
Scheduled
The USB is waiting for
startup
scheduled startup.
waiting
BS signal
The BS signal is stopped.
stopped
Remote
The remote signal is
signal
stopped.
stopped
Charge
The UPS is waiting for
OFF
ON
waiting
charging.
AC input
AC input voltage error-
error-VH
Voltage High
AC input
AC input voltage error-
error-VL
Voltage Low
AC input
AC input frequency error-
error-FH
Frequency High
AC input
AC input frequency error-
error-FL
Frequency Low
Message at
Output Charge
top
The self-diagnostic test
ON
Fault-E10
result indicates battery
deterioration.
ON
Battery
The battery reached end of
(Note 2)
end of life
life.
Charging is stopped
Fault-E12
because the battery
(Note 3)
temperature is high.
ON
(Note 2)
Charging is stopped
Fault-E14
because the battery
temperature is low.
The battery is not
OFF
ON
Fault-E11
connected.
○: Lit ON ●: Lit OFF
Description
Solution
-
-
-
The UPS cannot start
up due to
undercharge.
Use in the AC input
voltage range and
frequency described
in the specification.
Note: You can check
the input voltage by
selecting
"Measurement" menu
- "Input and Output".
○: Lit ON ●: Lit OFF
Description
Solution
Replace the battery.
Check that the
ambient temperature
of the UPS is
between 0 and 40
degrees Celsius.
Check the battery
cable connection.
BL50T/BL75T/BL100T

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bl100tBl75t

Table of Contents