INSTALLATION
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
Minimum Clearance from Top of Front Facing:
Mantel
min. 8"
(203mm)
Ceiling
39"
(990mm) from top of front facing
above louvers.
Side Wall:
6"
(152mm)
Horizontal Vent Clearances:
Top
2-1/2"
(64mm)
Side
1-1/2"
(38mm)
Bottom
1-1/2"
(38mm)
Vertical Vent Clearances:
1-1/4"
(32mm)
Alcove Clearances:
Max. Depth
36"
(914mm)
Min. Width
60"
(1524mm)
Min. Height
80"
(2032mm)
8
CLEARANCES
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
fi replace and vent system be installed only in
accordance with these instructions.
The HeatWave Duct Kit
and the Heat Release Kit
have different clearance
and framin requirements,
check the HeatWave and
Heat Release Kit
Heat Release manual for
details.
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
®
Regency
P48-2 Zero Clearance Direct Vent Gas Fireplace