Mantels; Mantel Leg Clearances - Regency P48-2 Owners & Installation Manual

Regency gas fireplace owners & installation manual
Hide thumbs Also See for P48-2:
Table of Contents

Advertisement

Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from louver are shown
in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible
board.
Combustible mantel leg clearances as per diagram:
®
Regency
P48-2 Zero Clearance Direct Vent Gas Fireplace

MANTELS

MANTEL LEG CLEARANCES

Maximum
1-1/2" projection at 3"
minimum clearance.
INSTALLATION
This drawing is to scale at 1:6 (one inch = 6
inches)
Mantel can be installed anywhere in shaded area
using the above scale for units with the Flush
Front and with the optional Bay Front.
Note: Ensure the paint that is used
on the mantel and the facing is
"heat resistant" or the paint may
discolour.