In addition you can change the parameterized properties via the user program in RUN mode.
When you assign parameters in the user program, the "WRREC" instruction transfers the
parameters to the module using data records (see appendix Configuration via parameter
data records (Page 72)). The following table summarizes all the configurable parameters.
Table 8- 1
AI Energy Meter 400VAC ST parameters
Parameters
Diagnostics line voltage •
Connection type
Voltage measuring
range
Line voltage tolerance
[%]
Line frequency
Enable gate energy
counter
User data variant
Diagnostics
overflow current
Diagnostics
overflow voltage
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Manual, 10/2017, A5E36061895-AB
Value range
Disable
Enable
•
Disabled
•
1P2W - 1-phase
•
alternating current
3P4W - 3 phases, 4
•
conductors
100 V
•
110 V
•
115 V
•
120 V
•
127 V
•
190 V
•
200 V
•
208 V
•
220 V
•
230 V
•
1 ... 50 %
•
50 Hz
•
60 Hz
•
No
•
Yes
•
See the table Overview
of the user data variants
(Page 92)
Disable
•
Enable
•
Disable
•
Enable
•
Default setting
Reconfigurati-
on in RUN
Disable
Yes
3P4W - 3 pha-
Yes
ses, 4 conduc-
tors
230 V
Yes
10 %
Yes
50 Hz
Yes
No
Yes
Total energy L1
Yes
L2 L3 (ID 254 or
FE
)
H
Disable
Yes
Disable
Yes
Parameters
8.1 Parameters
Effective range with configuration
software, e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Module
Module
(only 1P2W,
3P4W
and deacti-
vated)
Module
Module
Module
Module
Module
Module
Module
-
Module
Module
(only user data
variant)
Channel/phase
Module
Channel/phase
Module
55