Interrupts/diagnostic alarms

9.3 Diagnostic alarms

9.3
Diagnostic alarms
Diagnostic alarms
Note
Assignment channel in diagnostics alarm ⇔ Phase
Channels are counted in the diagnostic messages starting from channel "0" and in the
AI Energy Meter 400VAC ST starting from phase "1".
Note the following assignment:
• Channel "0" ⇔ Phase "1"
• Channel "1" ⇔ Phase "2"
• Channel "2" ⇔ Phase "3"
Table 9- 5
Error types
Diagnostic message
Undervoltage
1
Overvoltage
Overload
High limit
Low limit
1
Error
Parameter assignment
error
Load voltage missing
Channel is temporarily
unavailable
If the "Undervoltage" and "Low limit" diagnostics are active at the same time, the "Low limit" diagnostics has higher
1
priority and deletes the "Undervoltage" diagnostics.
64
Error code
Meaning
2
Line voltage (measuring range) is monito-
H
red for tolerance. Violation leads to voltage
3
H
overflow/underflow
4
The measured current is monitored after
H
expiry of the "Tolerance time" for "Tole-
rance value overcurrent [0.1 A]". Excee-
ding this results in overflow current.
The maximum value of the secondary
current (12 A) has been exceeded.
7
Cumulative overflow in the calculated va-
H
lues
8
Violation of the low limit for voltage measu-
H
rement. The message occurs when the
configured minimum current or voltage is
below 80 V.
9
Internal module error (diagnostic alarm on
H
channel 0 applies to the entire module).
10
The module cannot evaluate parame-
H
ters for the channel.
Incorrect parameter assignment.
11
Missing or insufficient line voltage on pha-
H
se L1
1F
Firmware upgrade is being performed.
H
Channel 0 applies to the entire module.
The module is currently not performing any
measurements.
A user calibration is being executed at the
channel.
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Solution
Observe the line voltage range
Observe the current range
-
Observe the voltage range
Replace the module
Correct the parameter assignment
Check supply
--
Complete the user calibration
Manual, 10/2017, A5E36061895-AB