User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Basic variables phase-specific measurement L1 (ID 159 or 9F
Table D- 12
Basic variables phase-specific measurement L1
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 to 3
Current L1
4 to 5
Voltage UL1-N
6 to 7
Active power L1
8 to 9
Reactive power L1
10 to 11
Apparent power L1
12 to 15
Active energy L1 total (inflow - outflow)
16 to 19
Reactive energy L1 total (inflow - outflow)
20 to 23
Apparent energy L1
24
Scaling current L1
25
Scaling active power L1
26
Scaling reactive power L1
27
Scaling apparent power L1
28
Scaling active energy L1 total (inflow - outflow)
29
Scaling reactive energy L1 total (inflow - outflow)
30
Scaling apparent energy L1
31
Power factor L1
102
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
)
H
Data
Unit
Value range
type
BYTE
-
159 (9FH)
BYTE
Bit
qq xx xx xx
string
UINT
1 mA
0 to 65535
UINT
0.01 V
0 to 65535
INT
1 W
-27648 to 27648
INT
1 var
-27648 to 27648
INT
1 VA
-27648 to 27648
UDINT
1 Wh
0 to 2147483647
UDINT
1 varh
0 to 2147483647
UDINT
1 VAh
0 to 2147483647
USINT
-
0 to 255
USINT
-
0 to 255
USINT
-
0 to 255
USINT
-
0 to 255
USINT
-
0 to 255
USINT
-
0 to 255
USINT
-
0 to 255
USINT
0.01
0 to 100
Manual, 10/2017, A5E36061895-AB
Mea-
sured
value
ID
-
-
66007
66001
66013
66016
66010
62115
62116
62114
-
-
-
-
-
-
-
66019